On boats in Europe you will meet two main sets of standards for electrical installations: the European ISO 13297, which the CE mark is based on, and the American ABYC standards. Both aim for the same thing: an installation that does not catch fire, does not give shocks and works reliably at sea. But they describe it in different ways.
My experience tells me one thing: ABYC says much more precisely what to do and how to do it. It gives concrete distances, values, test procedures and exceptions, often explaining the reasoning too. ISO 13297 more often states a requirement in general terms and leaves the details to the installer.
Here are a few concrete examples from practice.
ISO 13297:2020 (in Europe EN ISO 13297:2021) covers AC and DC installations on small craft up to 24 m. It replaced the earlier ISO 10133. It is harmonised with Directive 2013/53/EU, so yards building CE-marked boats base their electrical installations on it. The whole standard runs to a few dozen pages.
ABYC (American Boat & Yacht Council) is a US organisation that has been writing standards for boats since the 1950s. Electrical systems are covered by a whole series of separate standards:
E-11 on its own is more than twice the length of the whole of ISO 13297, and batteries and switches have their own standards on top. That alone shows the difference in approach.
ISO 13297 (clause 8.2): once installed, a battery must not move more than 10 mm in any direction under a force equal to twice its weight.
ABYC E-10: the same idea of a force of 2× the battery's weight, but the permitted movement is 25 mm. In return, ABYC describes exactly how to carry out the test:
On top of that, for lithium batteries ABYC E-13 requires no visible movement where the manufacturer gives no guidance. For offshore boats it also takes knockdowns and hull slamming into account.
Takeaway: ISO has the stricter value, but ABYC tells you unambiguously how to check it. A good installer takes the 10 mm from ISO and the test procedure from ABYC.
ISO 13297 says very little about terminals:
ABYC E-10 gives concrete rules you can check at every inspection:
Takeaway: ISO tells you the connection has to be good. ABYC tells you exactly what it should look like.
ISO 13297 (clauses 8.6–8.7): a battery must not be installed directly above or below a fuel tank or fuel filter without a separating structure. Metal fuel-system components within 300 mm above the battery must be electrically insulated.
ABYC E-10: batteries must not be installed above or below a fuel tank, fuel filter or fuel fitting. The zone is 305 mm from the plane of the battery terminals, horizontally and vertically. ABYC adds clarifications that settle the usual doubts:
Takeaway: the values are almost the same, but only ABYC answers the questions an electrician actually asks on board.
Here both standards are equally precise, which shows that ISO can be specific too:
| ISO 13297 (clause 12.1) | ABYC E-11 | |
|---|---|---|
| Fuse from the power source, measured along the cable | 175 mm | 178 mm (7 in) |
| Sheathed cable, from the battery terminal | up to 1.8 m | up to 183 cm (72 in) |
| Sheathed cable, from another source | up to 1 m | up to 102 cm (40 in) |
| Starter motor cables | exempt | exempt |
The difference is in the detail. The 2025 edition of ABYC E-11 lists the self-limiting devices by name that need no fuse at their output: alternators, battery chargers, DC/DC converters, solar panels, wind generators and fuel cells. It also gives the condition: the cable's ampacity must be at least equal to the device's rated output.
This is the biggest difference between the two standards.
ISO 13297 requires in general terms that the protection interrupts an overcurrent before the cable insulation overheats. It does not say what short-circuit current the fuse must be able to interrupt.
ABYC E-11 (2025) is very specific:
A 300 Ah LiFePO4 bank works out at around 15,000 A of short-circuit current. ISO will not tell you that your fuse may be unable to interrupt it. With ABYC you can work it out in a minute.
ISO 13297 (clause 9.2) and ABYC E-11 agree that the switch's 30-second rating must be at least equal to the starter motor current, and its continuous rating must match the protection downstream.
ABYC, however, has a separate standard, C-7, that describes the switch itself:
ISO, on the other hand, has two requirements that ABYC does not have in this form. A battery switch is required for practically every battery, and a remote-controlled switch must also allow manual operation.
ISO 13297 does not cover lithium batteries at all; they have a separate standard, ISO 23625.
ABYC E-13 describes lithium installations in great detail, including:
To keep the comparison fair: ISO 13297 is sometimes stricter in its values.
| Topic | ISO 13297 | ABYC |
|---|---|---|
| Battery movement in the force test | 10 mm | 25 mm |
| When a battery switch is required | practically always | above 800 CCA or 100 Ah (lithium: 500 Wh) |
| Equipment connected ahead of the switch | each with its own fuse close to the battery | permitted |
| Heel | no electrolyte leakage up to 30°; on sailing monohulls, electrolyte containment up to 45° | recommendation on battery orientation |
| Remote battery switch | must also have manual operation | status visible at the control |
My rule for refits is simple:
The result is an installation that stands up to any surveyor or insurer, whichever standard they assess it against. Above all, it is simply safer.