You switch to LiFePO4, install a 300 Ah bank and fit a 250 A fuse at the battery. Everything looks right: the fuse is close to the terminal and its rating suits the cable. But in a short circuit that fuse may not stop the current. The fuse element melts, an electric arc forms inside, and it keeps burning until something melts or bursts.
In this article I explain why that happens, how to work it out, and what ABYC E-11 says in its 2025 edition, which brought important changes here. It is rarely discussed in Europe, because the European standard ISO 13297 does not cover it in detail. You can read more about the differences between the standards in ABYC vs ISO 13297: comparing the standards.
Every fuse has two important ratings that are easy to confuse:
If the short-circuit current is higher than the interrupting capacity, the fuse cannot deal with the arc that forms as its element melts. The result can be current still flowing through the arc, a burst fuse body and a fire.
The current rating is always printed on the fuse. The interrupting capacity usually has to be looked up in the manufacturer's data sheet.
Short-circuit current depends on the battery's internal resistance. Lithium batteries, LiFePO4 included, have very low internal resistance, so in a short circuit they deliver an enormous current, far more than a lead-acid battery of the same capacity.
ABYC E-11 (2025 edition, clause 11.10.1.3.2) says that where the manufacturer does not state the battery's short-circuit current, it is calculated as follows:
| Battery type | Short-circuit current per 100 Ah |
|---|---|
| Lead-acid (other than TPPL) | 3,000 A (3 kA) |
| Lithium-ion, LiFePO4 included, and TPPL lead-acid | 5,000 A (5 kA) |
TPPL batteries are lead-acid batteries with thin plates of pure lead. Their internal resistance is low, so the standard treats them like lithium.
If the manufacturer does state the short-circuit current, use their figure. E-13 in fact requires the maker of a lithium battery to state in its documentation the maximum short-circuit current in the event of a BMS failure.
In parallel, the batteries' short-circuit currents add up. In series they do not. The standard gives an example that shows this well: six 6 V batteries wired into a 12 V bank (three strings of two batteries in series) have a short-circuit current three times that of one battery, not six times.
The previous edition treated all batteries in much the same way. The new one draws a clear line.
The minimum interrupting capacity of the main fuse is read from a table in the standard, according to battery size and system voltage. For example, in a 12 V system with a lead-acid bank of up to 140 Ah, the main fuse needs an interrupting capacity of at least 1,500 A.
This covers LiFePO4 and other lithium batteries, AGM, gel, TPPL, and lead-acid banks above 2,200 CCA or 500 Ah. The main fuse's interrupting capacity must be:
Parallel banks above 500 Ah need an additional fuse between each battery and the main fuse, meeting the same interrupting capacity requirements. It is a safety fuse, fitted in addition to the main one.
The interrupting capacity requirements now also cover branch circuit fuses. Small devices are the exception: up to 30 A at 12 V, 15 A at 24 V, 10 A at 36 V and 7.5 A at 48 V, as are solid-state (electronic) protection devices.
The standard points out that a fuse manufacturer's interrupting capacity applies to a specific voltage and usually falls as the voltage rises. A fuse that interrupts 10 kA at 12 V may interrupt much less at 48 V. On 24 V and 48 V systems this needs checking with particular care.
ABYC E-13 for lithium batteries is clear: if necessary, the bank must be subdivided into smaller units so that the interrupting capacity of the protection devices is not exceeded. In practice that means several smaller banks, each with its own fuse.
The European standard ISO 13297 requires in general terms that protection interrupts an overcurrent before the cable insulation overheats, and that it is coordinated with the circuit. It does not say what short-circuit current the fuse must be able to interrupt, or how to work it out. Lithium batteries are covered by a separate standard, ISO 23625.
For lithium installations it is therefore worth turning to ABYC, which says exactly what to calculate and which fuse to use.
The fuses commonly used on boats vary widely in interrupting capacity. The highest is usually found in Class T fuses, designed specifically to protect large battery banks; their interrupting capacity typically reaches 20 kA. Other popular types, mounted directly on the terminal or in fuse holders, often have a much lower interrupting capacity. I always check the data sheet for the specific fuse, at the specific system voltage.
| Requirement | ISO 13297 | ABYC E-11 (2025) |
|---|---|---|
| Main fuse interrupting capacity | no detailed requirements | from a table (flooded lead-acid) or from short-circuit current (others) |
| Short-circuit current if not stated by the manufacturer | not defined | 3 kA/100 Ah lead-acid, 5 kA/100 Ah lithium and TPPL |
| Fuse at each battery | no | in parallel banks above 500 Ah |
| Branch circuits | no | requirements above 30 A at 12 V |
| Subdividing the bank | no | E-13: if interrupting capacity is not enough |
Planning a switch to LiFePO4, or want your existing installation checked? I will work out your bank's short-circuit current and choose protection to ABYC E-11 and E-13. Write or call me, including on WhatsApp: +39 351 384 9089 or +48 791 74 74 54.
Grzegorz Szubert, Yacht Electrical Services, ABYC member